    What causes a 4-20mA loss (LFF) on an ATV312 drive?

    Issue:
    What causes a 4-20mA loss (LFF) on an ATV312 drive?

    Product Line:
    Altivar 312

    Environment:
    All

    Cause:
    Loss of 4-20mA on AI3.

    Resolution:
    This will happen if the LFF is programmed to a function other than ignore (no).
    If it is programmed to a function other than no, then the drive is designed to have a value of 4 mA minimum (unless CRL3 is changed to 0 instead of 4A) on AI3 input.  