Discover our Clipsal Smart Home packages as seen on the Block

in location

OR

I'm looking for

  • Wholesalers
    • Uncheck All Check All
  • EXPERTISE
    • Expand
    • Expand
    • Expand
    • Uncheck All Check All
  • Switchboard Manufacturers
    • Uncheck All Check All
OR

The best way to see what Clipsal electric products can do for your home is seeing them in action at a Clipsal Display Centre.

Product stock may vary according to location. If you're after a specific product range, please check with your chosen location before visiting.

10 Results
    Load More Load Complete
    Change Location

    What is an internal serial link fault (INF3) on an ATV320 drive?

    Issue:
    What is an internal serial link fault (INF3) on an ATV320 dirve?

    Product Line:
    Altivar 320

    Environment:
    All

    Cause:
    Communication interruption between internal cards of VFD

    Resolution:
    Check internal connections.  
    If there is an option card, remove and re install.
    Power cycle the VFD.  
    Factory reset if needed.
    Power up with no option card if instaled (this will perform factory reset)

    Didn’t find what you were looking for?

    Try Searching Again View Our Categories

    Need further assistance?

    Our Customer Care department provides total customer service solutions for our residential, industrial and commercial applications.

    Get Assistance