    How to setup an external fault function on the ATV212 drive?

    Issue:
    How to setup an external fault function on the ATV212 drive?

    Product Line:
    Altivar 212

    Environment:
    All

    Cause:
    Configuration

    Resolution:
    To set an external function you will need to program one of the logic inputs F/R/or RES as external fault.
    Under F--- menu.
    F111 is F
    F112 is R
    F113 is RES terminals.
    Let assume you want to program R as external fault function.
    Set F112 to 11 for external fault where OFF is no detected fault and ON is where motor stops according to method set by parameter Ext fault stop mode (F603).  
    This will prompt E on display if external fault is on.
    F603 options: 0 for freewheel, 1 for ramp stop, 2 for DC breaking stop.