    PowerSCADA Expert 8.2 Update 5 - Release Notes

    Issue
    What is new in PSE8.2 and a detailed listing of resolved problems and minor enhancements.

    Product Line
    PowerSCADA Expert 8.2 (PSE8.2)

    Environment
    Installer
     
    Cause
    A new PSE8.2 cumulative update release.

    Resolution
    PowerSCADA Expert 8.2 Update 5 - Release Notes
    Release Notification (Updated 25 April 2018)

    This is a detailed listing of resolved issues and minor enhancements in this release.  


     

    Prerequisite

    You must have PowerSCADA 8.2 installed prior to installing this update. No previous updates are required.

    Cybersecurity Announcement

    Floating License Manager v2.1 addresses vulnerabilities in the Flexera FlexNet Publisher component detailed in CVE-2016-10395, CVE-2017-5571 and CVE-2016-2177. Uninstall the current version of the Floating License Manager, and then install version 2.1.
    NOTE: The Floating License Manager v2.1 installer is included with this hotfix release but is not a part of the hotfix installer. Unzip "Floating License Manager v2.1.zip" and run "setup.exe".

    Important Notice: There is a known issue with the Floating License Manager v2.1.0.0 installer. When installing with a logged-in Windows User name containing a space, the install will not succeed. The workaround is to install the Floating License Manager with a user that does not include a space character in their name.

    Bug Fixes and Enhancements

    TFS 21482 - AlarmEvents with a state of normal returned in GetAlarmEvents response for EWS
    GetAlarmEvents was changed to not return alarms in the normal state.

    TFS 21483 - Incorrect timestamp information provided for AlarmEvents not in the Active state
    Alarm timestamps are now updated to reflect the true timestamp of occurrence for all state changes (active, drop out, acknowledge).

    TFS 21484 - Unable to filter AlarmEvents by Type using EWS
    Alarms are now filtered based on type. 

    TFS 21485 - Unable to successfully acknowledge alarms using EWS
    In some situations, EWS would not acknowledge alarms correctly.  This behavior has been fixed.

    TFS 21486 - Unable to filter alarms using the PriorityTo and PriorityFrom fields
    EWS did not observe the priority field correctly. This has been addressed and the minimum allowable priority has been set to 1 (to exclude non-alarm objects in the PowerSCADA alarm database).

    TFS 21557 - PowerSCADA projects - including the starter project, PLS_Include, and PLS_Example - need to be upgraded to support the new DBF schemas
    PowerSCADA projects have been upgraded to the latest DBF schemas.  If there are existing projects created from the starter project, set [CtEdit] Upgrade = 1 in the Citect.ini file using the Setup Editor, and then restart PowerSCADA Studio.

    TFS 21564 - Alarm Proxy does not show the analog alarm states
    Alarm Proxy now reports the analog alarm states (HIGH HIGH, HIGH, LOW, LOW LOW) instead of ON / OFF.

    TFS 21566 - If a CSV file that does not exist is selected in the I/O Device Manager, the application throws a runtime exception
     

    A message is displayed indicating that the file does not exist.

     

    TFS 21569 - On large systems with 200k configured alarms, the GetAlarmDefinitions call in Alarm Proxy is slow and causes ENM to timeout
    Performance issue in alarm proxy has been resolved.

    TFS 21649 - When CoreServiceHost adds and removes devices, it may lose the original IDs
    CoreServiceHost now keeps a device chronicle.  When the device is removed and then later added, the ID will remain the same.

    TFS 21913 - If the equipment name is changed in the system, but the I/O Device name is unchanged, CoreServiceHost will not refresh the equipment name
    CoreServiceHost now properly updates the equipment on name change.

    TFS 21935 - Logs that are too large for the Windows Event Log do not get logged properly
    Large logs are now broken down into smaller log entries.

    TFS 21970 - Profile Wizard and Automation does not support IPv6
    Profile Wizard and Automation now supports IPv6 for TCP/IP Board level drivers.  This requires the TCP/IP Driver version 4.0.0.0 or later.

    TFS 21975 - Open and Close buttons are disabled at runtime on equipment popup when separate digital tags are used for commands
    The form now enables the command buttons if the Pos_On or Pos_Off tags are defined.

    TFS 21979 - Alarm Proxy cannot return alarms that transition to inactive
    This setting is now configurable in the Application Configuration Utility.

    TFS 22043 - Single sign-on calls from a remote thick client do not work
    Single sign-on now detects remote clients.

    TFS 22060 - The I/O Device Manager cannot bulk import devices with device names greater than 16 characters
    The I/O Device Manager now reads the device name length from the equipment.profiles file for proper validation.

    TFS 22066 - Wonderware ArchestrA Logger Security Patch
    Wonderware ArchestrA Logger Patch 2017.517.2328.1 is applied.

    TFS 22150 - Alarm filters do not work on some resolutions
    Alarm filter AN numbers are fixed for all alarm page resolutions.

    TFS 22155 - Alarm filters perform exact matching
    The alarm filter screen allows the user to select the filtering mode. The default setting is read from the INI file [Alarm] FilterMode.  0 (default) = Exact Match, 1 = Starts With, 2 = Ends With, 3 = Contains.

    TFS 22306 - The equipment tree used on alarm pages is slow to render over the web client
    Any page using the equipment tree should set the default library and symbol on the equipment tree genie, or set 'Hide Symbol Icons' to 'TRUE' if a default icon is not available.

    TFS 22401 - Alarm filter and equipment tree filter operate independently
    The alarm filter and equipment tree filter operate together to filter the alarm tables.

    TFS 22896 - Core service host logs two warnings during shutdown - exception thrown during disposal.
     

    Cleanup methods were reworked to prevent the exception.

     

    TFS 22898 - EWS cannot obtain tag updates at a 5 second rate
    EWS and core services were updated to obtain data at a 5 second poll rate.

    TFS 23262 - Equipment popup alarm table does not acknowledge or disable alarms
    Alarms can now be acknowledged or disabled in the equipment page.

    TFS 23274 - Equipment.profiles cannot be imported into the Profile Editor in cases where the original Device Types and Device Profiles were lost
    The Profile Editor can import the equipment.profiles file to generate device types, device profiles, and tags.

    TFS 23437 - Citect 2016 Updates
     

    Citect 2016 Update (April 10, 2018) is included with this update.

    Project ID management was removed from Citect 2016.  Project IDs are now located in the ProjectInfo.xml file. 

    MinUnitNumber and MaxUnitNumber (previously stored in UnitNumberRange.xml) have also been migrated to ProjectInfo.xml.

     

    TFS 23637 - The Alarm Summary page does not display state information
    The Alarm Summary page now displays the state that caused the alarm.

    TFS 23650 - 8.2 install does not enable ASP feature within IIS
    The installer now enables the ASP feature under IIS. This server role feature is required to run the Citect web control client. (Previously the View-Only web client was the only option for web deployment.)

    TFS 24205 - When Core Services receives a timeout from the Client, alarm processing may halt until the service is restarted
    Core Services properly recovers from a ctApi deadlock condition.

    Files Modified

    Applications\AppServices\bin\Framework.dll
    Applications\AppServices\bin\Framework.ServiceHost.exe
    Applications\AppServices\bin\Modules.CoreServices.dll
    Applications\AppServices\bin\PowerLogic.Cipher.dll
    Applications\AppServices\bin\Modules.ProviderBase.dll
    Applications\AppServices\bin\Modules.ProviderEngine.TestHarness.exe
    Applications\AppServices\bin\ObjectFactoryTools.exe
    Applications\AppServices\bin\ProviderGatewayProviders.dll
    Applications\AppServices\bin\PowerSCADA.Common.dll
    Applications\AppServices\bin\Modules.Platform.Citect.dll
    Applications\EWS\bin\Framework.dll
    Applications\EWS\bin\EWS.dll
    Applications\EWS\Web.config
    Applications\EWS\DataExchange.svc
    bin\de\ProfileEngine.resources.dll
    bin\de\ProfileWizard.resources.dll
    bin\de\WizardLibrary.resources.dll
    bin\es\ProfileEngine.resources.dll
    bin\es\ProfileWizard.resources.dll
    bin\es\WizardLibrary.resources.dll
    bin\fr\ProfileEngine.resources.dll
    bin\fr\ProfileWizard.resources.dll
    bin\fr\WizardLibrary.resources.dll
    bin\it\ProfileEngine.resources.dll
    bin\it\ProfileWizard.resources.dll
    bin\it\WizardLibrary.resources.dll
    bin\ja\ProfileEngine.resources.dll
    bin\ja\ProfileWizard.resources.dll
    bin\ja\WizardLibrary.resources.dll
    bin\ko\ProfileEngine.resources.dll
    bin\ko\ProfileWizard.resources.dll
    bin\ko\WizardLibrary.resources.dll
    bin\ru\ProfileEngine.resources.dll
    bin\ru\ProfileWizard.resources.dll
    bin\ru\WizardLibrary.resources.dll
    bin\zh-chs\ProfileEngine.resources.dll
    bin\zh-chs\ProfileWizard.resources.dll
    bin\zh-chs\WizardLibrary.resources.dll
    bin\zh-cht\ProfileEngine.resources.dll
    bin\zh-cht\ProfileWizard.resources.dll
    bin\zh-cht\WizardLibrary.resources.dll
    bin\ProfileAutomation.dll
    bin\ProfileEngine.dll
    bin\ProfileWizard.exe
    bin\WizardLibrary.dll
    bin\ProfileAutomationUtility.exe
    bin\CommsMethodProperties.xml
    bin\DeviceManagementUserControlLibrary.dll
    Applications\Profile Editor\Tags.xml
    Applications\Profile Editor\ProfileEditor.Business.dll
    Applications\Profile Editor\ProfileEditor.exe
    Applications\Profile Editor\ProfileEditor.UserControls.dll
    Applications\Profile Editor\Resources\ProfileEditor.UserControls.resources
    User\PLS_Include\*
    User\PLS_Example\*
    Starter\Default_Starter.ctz

    Installation

    Unzip "PowerSCADA Expert 8.2 Update 5.zip" and run "PowerSCADA Expert 8.2 Update 5.exe".