    Galaxy 5000; Modbus Q1 Input Breaker status does not change state

    Issue:
    Modbus Q1 Input Breaker status does not change state

    Product line:
    NAM Galaxy 5000


    Environment:
    NAM Galaxy 5000


    Cause:
    Modbus Q1 Input Breaker status does not change state

    Resolution:
    The 66061 JBUS/Modbus manual was updated May 2018 to reflect the correct Modbus register for NAM Galaxy 5000 Q1 Breaker status.  The Q1 Modbus register is only monitored on EMEA Galaxy 5000/5500 UPSs.  For NAM Galaxy 5000 customer must monitor KA1 for Q1 Breaker status change.  EMEA UPSs can monitor the KA1 status as well but KA1 is optional on EMEA UPSs.
    From the 66061- JBUS/Modbus manual
     
    Status message   Status to 0 Status to 1 JBUS Word Bit
    Mains 1 input switch (Q1) in EMEA closed open 44 3
    Mains 1 backfeed (KA1 optional) closed open 44 6
    Converted to Modbus
    Status message   Status to 0 Status to 1 Modbus Bit
    Mains 1 input switch (Q1) in EMEA closed open 69 3
    Mains 1 backfeed (KA1 optional) closed open 69 6
     


     