    What are the switchgear control failure codes?

    • A code appears in Event log for each control operation:
    Code      Reason
    0              Command completed successfully
    1              Local command blocked because switch position is intermediate or unknown
    2              Local command blocked because switch position is already in correct state
    3              Local command canceled by user
    4              Switch position did not change within configured maximum operation time
    5              Command blocked by Head Unit interlocks, e.g. motor supply fault or battery low
    6              Command failed due to timeout waiting for enable from Head Unit
    7              Local command blocked because disabled by configuration
    8              Local command blocked because local/remote status is unknown
    9              Local command blocked because local/remote status is remote
    10           Local command blocked because automation is on
    11           Remote command blocked because automation is on
    12           Sectionalizer command blocked because automation is off
    13           Sectionalizer command blocked because local/remote status is unknown
    14           Sectionalizer command blocked because local/remote status is local
    15           Unexpected command source (firmware error)
    16           Remote command blocked because requested position is not a valid value
    17           Command blocked because a command is already in progress for this module
    18           Command blocked because the power shutdown signal is active
    19           Command blocked because a command is already in progress for another module
    20           Command blocked because measured switch position is intermediate or unknown
    21           Command blocked because measured switch position is the same as the requested position
    22           Command blocked because earth switch position is open
    23           Open command blocked because external input is false
    24           Open command blocked because external input is true
    25           Close command blocked because external input is false
    26           Close command blocked because external input is true
    27           Commands blocked because module behaviour mode is off
     