    Video: How to configure a register through ION Setup 3.0

    Issue
    Configuring Modbus Registers on PowerLogic ION Meters via ION Setup

    Product Line
    PM8000
    ION8650
    ION8600
    ION7650, ION7550
    ION7600, ION7500, ION7400

    Environment
    ION Setup 3.0

    Cause
    Would like to map values that aren't already mapped in the Modbus register map

    Resolution
    Follow the steps to configure a register in ION Setup 3.0

    Open ION Setup 3.0 > View Setup Screens > Open Setup Assistant

    Navigate to Communications > 3rd Party Protocols > Modbus Slave tab



    Click on the Map name to highlight to Edit the map



    Click Add, then configure the parameters of the custom register.
    Note: the Address value must be between 40001 & 41800



    Select a Source Register to link



    Click Ok after parameters are chosen

    Can save the Modbus map as a CSV by clicking on 'Save As' and choosing a file location. Click Ok

    Now a Modbus register has been added/configured and can read this register's value

    Note: For documentation on ION Modules, please reference ION Reference