    What is the demand interval range for the PM8000?

    Issue
    What is the demand interval range for the PM8000

    Product Line
    PM8000 series meter
    PM8240
    PM8243
    PM8244

    Environment
    ION Setup
    User Guide, Meter Configuration, Settings and Characteristics

    Cause
    Need to know the range the demand sub-interval length can be set to in the PM8000 series meter.

    Resolution
    The demand sub-interval length value must be between 1 second and 99 minutes.

    To configure the meter's Demand interval using ION Setup:
    1. Start ION Setup.
    2. Open the Setup Assistant for your meter.
    3. Navigate to Demand > Rolling Block.
    4. Configure the Sub-interval Length by selecting the parameter and clicking Edit.
    5. Once the parameter has been configured, click OK to save the setting to the meter.