    How do I disable the remote HMI (VW3A1101) loc/ rem button used with an ATV212?

    Issue:
    How do I disable the  remote HMI (VW3A1101) loc/ rem button used with an ATV212?

    Product Line:
    ATV212 

    Environment: 
    All serial numbers 

    Cause:
    Unwanted function

    Resolution:
    Loc/rem key]   (F732) to 1       [Prohibited]     
    F732 [Loc/rem key] 0
    Use parameter F732 to enable or disable the LOC/REM key on the drive embedded display terminal. If the LOC/REM key is disabled, switching between local and remote mode can be achieved with parameters [Frequency mode sel]  (FMOd) and [Command mode sel] (CMOd). 
    0 = [Permitted memo]: still retained with the power off.
    1 = [Prohibited]
    2 = [Permitted no memo]: cancelled with the power off. 