    Is it possible to run ATV drives with step-up transformer at the output?

    Issue:
    Is it possible to run ATV drives with step-up transformer at the output?
     
    Product Line:
    Altivar Drives
     
    Environment:
    All
     
    Cause:
    Altivar Drives with step-up tansformer
     
    Resolution:
    For Altivar Process it is possible to run step-up solution (ATV drive + sinus filter + step up transformer + motor). There is no special version necessary like S387 that was needed for ATV61
    So we can offer ATV930/ATV950/ATV960/ATV980 with sinus filter for step-up solutions.
    Required settings for transformer on the output:
    [Motor Control Type] Ctt = U/f 5pts
    [Sinus Filter Activation] OFI = Yes
     
    For ATV machine (ATV320, ATV340) there is not such possibility. First, ATV machine offer is dedicted for machines that have limited power range and second, they the machines use standard voltage class. No sinus filter exist for ATV320/340

    Contact your local Drives PAE, Product Application Engineer for further assistance with this application.