    How do you configure a relay output on ATV630/930 to indicate safety input status?

    Issue:
    On the Altivar Process 630/930, we need a relay to indicate if safety input is active or not

    Product Line:
    Variable Frequency Drives

    Environment:
    Applies to Altivar Process 630 and 930

    Cause:
    We need to have an indication when the safety circuits on the drive STOA or STOB are open

    Resolution:
    You can configure one of the relays of the drive to "Power Removal State"

    Go to Complete Settings
    Go to Input/Output Relay
    Go to Rx Configuration
    Set Rx assignment to "Power Removal State"

    Replace x with the number of the relay you want to use.

     