    What is CFI2 fault mean on the ATV630 process drives?

    Issue:
    What is CFI2 fault mean on the ATV630 process drives?

    Product Line:
    Altivar 630, Process

    Environment:
    All

    Cause:
    Fault

    Resolution:
    This is a fault where the preset configuration has not been transferred properly usually through keypad download/transfer.
    This can happen if the configuration file that is being downloaded to the drive does not match the part number or firmware version of the downloaded VFD compared to the drive uploaded.
    If the fault does not go away on power up after power cycle then perform a factory reset 