    PME 8.x: An HTTP Error 500.19 - Internal Server Error is shown when attempting to access Dashboards and/or Reports

    Issue
    An HTTP Error 500.19 - Internal Server Error is shown when attempting to access Dashboards and/or Reports. The requested page cannot be accessed because the related configuration data for the page is invalid. Error Code: 0x800700c1.



    Product Line
    Power Monitoring Expert (PME) 8.x

    Environment
    Web Applications

    Cause
    This error occurs as a result of the DynamicCompressionModules and StaticCompressionModule being installed when Windows Server Update Services (WSUS) is installed on the same machine.


    Resolution
    1. Open IIS
    2. Click on server module node at the top of the left hand tree and choose "Modules".
    3. Right click on DynamicCompressionModule and choose "Unlock"
    4. Right click on StaticCompressionModule and choose "Unlock".
    5. Open desired websites -> Open Modules.
    6. Right click on DynamicCompressionModules and choose "remove".
    7. Right click on StaticCompressionModule and choose "Remove".
    8. Restart IIS.