    Does the PSO PM5000S1 driver support DebugCategory and DebugLevel parameters?

    Issue
    Power SCADA Operation does not appear to support citect.ini parameters for DebugCategory and DebugLevel, making it impossible to enable verbose debugging at the driver level.

    Product Line
    Power SCADA Operation 8.2 
    PowerSCADA Expert 8.1
    PowerSCADA Expert 8.0 SR1
    PowerSCADA Expert 8.0


    Environment
    Power SCADA Citect.ini

    Cause
    The PM5000S1 driver is a legacy driver supporting older versions of PM5000 firmware and it inherits driver parameters from the parent driver (PM5000S).

    Resolution
    Instead of trying to add driver parameters in the citect.ini file for the PM5000S1, simply add them for the PM5000S driver family and both of the PM5000 drivers will log as configured.