    How to set up an ATV320 with terminals as run command and 0-10VDC reference from AI1?

    Issue:
    How to set an ATV320 with terminals as run command and 0-10VDC reference from AI1?

    Product Line:
    Altivar 320

    Environment:
    All

    Cause:
    Programing

    Resolution:
    Wiring: 
    DI1 and +24V as 2 wire control run command.

    0-10VDC can be wired into AI1 and COM.
    If using a potentiometer then wiring would look like +10, Ai1, and COM.

    Drive is already programmed to do this function from the factory.
    Under CONF, FULL, I/O, TCC will need to be set to 2C.
    Under CONF, FULL, CTL, FR1 will need to be set to AI1