    Time on Power Monitoring Expert Server Changes to a Future Date in a Redundant System

    Issue
    The time on the PME server changes to 2084 or a similar year in the future.

    Product Line
    Power Monitoring Expert 8.1 (could apply to any version)
    everRun from Stratus Technologies (Marathon)

    Environment
    PME installed on a redundant system running on Marathon

    Cause
    A series of these events are in Windows Security Log:

    Log Name:      Security
    Source:          Microsoft-Windows-Security-Auditing
    Date:              7/30/2084 1:10:54 PM
    Event ID:        4616
    Task Category: Security State Change
    Level:              Information
    Keywords:       Audit Success
    User:              N/A
    Computer:      WIN-L9J7NRS9HL1
    Description:   The system time was changed.

    Subject:
        Security ID:               SYSTEM
        Account Name:          WIN-L9J7NRS9HL1$
        Account Domain:        WORKGROUP
        Logon ID:                   0x3e7

    Process Information:
        Process ID:    0xa34
        Name:        C:\Program Files (x86)\Citrix\XenTools\XenGuestAgent.exe

    Previous Time:        ‎2084‎-‎07‎-‎30T18:10:54.628000000Z
    New Time:              ‎2084‎-‎07‎-‎30T18:10:54.626000000Z

    This event is generated when the system time is changed. It is normal for the Windows Time Service, which runs with System privilege, to change the system time on a regular basis. Other system time changes may be indicative of attempts to tamper with the computer.

    Resolution
    As described above, the XenGuestAgent process is using System privilege to change the time.  A workarount would be to remove this priviledge:

    1. From Administrative Tools open Local Security Policy
    2. Navigate to Local Policies > User Rights Assignment

              

    3. In 'Change the system time' remove the SYSTEM group
    - open 'Change the system time' property window (double click on it)
    - select SYSTEM group
    - click on Remove