    How do I configure an ATV61 or ATV71 in MCC for Ethernet Control with a Hand-Off-Auto Selector?

    Issue:
    How do I configure control on an ATV61 or ATV71 in MCC for Ethernet Control with a Hand-Off-Auto Selector?

    Product Line:
    Altivar 61 Altivar 71 ATV61 ATV71

    Cause:
    Configuration

    Environment:
    Schneider Electric Motor Control Center

    Resolution:
    Forced Local is programmed from the factory and the IP Address goes away when the Forced Local contact is On. 
    Program as follows to prevent this;
       Command Menu
    Ref 1 channel: Com Card (Auto)
    Profile: Separate or I/O (*Depends on PLC Assemblies)
      (**Note:  If you set Profile to I/O, then need to change back, the drive is reset to factory settings)
    Cmd Ch1: Com Card
    Cmd Ch2:Terminals
    Cmd Switching: LI3
    Ref 2 Sw: LI3
    Ref 2 Ch:  AI1 (Hand)

      Communications Menu
    Forced Local
     Forced Local Assignment and Reference - Change to NO