    What protective devices are required for EV Chargers?

    Protective devices which are required for EV chargers can be either RCBO or MCB+RCCB. 

    For 1P 16A  => 3,7Kw load    protection devices = 20A curve C + type Asi 30mA 
    For 1P 32A  => 7Kw load       protection devices = 40A curve C + type Asi 30mA
    For 3P 16A  => 11Kw load     protection devices = 20A curve C + type B 30mA
    For 3P 32A  => 22Kw load     protection devices = 40A curve C + type B 30mA

    The circuit breaker value (20A or 40A) depends of the cable size, length and environmental parameters (up to the electrician)



     