    Video: How to take the Galaxy 5000 UPS from total power off to normal operation.

    Issue:
    Transitioning the Galaxy 5000 UPS from total power off to normal on-line operation.
     
    Product line:
    Galaxy 5000, Galaxy 5500
     
    Environment:
    All models, all serial numbers
     
    Cause:
    For various reasons, the Galaxy 5000 may be in a totally off state.  This guide illustrates how to restore it to normal operation.
     
    Note: This is not for commissioning a new UPS.  The commissioning of a new UPS must be performed by a Schneider Electric trained and qualified service representative.
     
    Resolution:
    How to restore the Galaxy 5000 UPS from total power off to normal operation.  This procedure is for a single UPS without an external bypass panel.
     
    These instructions are in the owner’s manual which can be located at http://www.apc.com/salestools/MBPN-8YPFLA/MBPN-8YPFLA_R0_EN.pdf
     
    Step 1: Set the input Q1 switch to On
    Step 2: Wait until the end of the UPS initialization with PFC start-up.
    Step 2: Push the Menu Button
    Step 3: Scroll to “Maintenance”
    Step 4: Choose “Start the UPS”
    Step 5: Turn the Q4S Switch to On
    Step 6: Turn the output switch Q5N to On
    Step 7: Turn the maintenance bypass switch Q3BP to Off
    Step 8: Set the battery circuit breaker(s) QF1 to the On Position.
    Step 9: Press the Green “Inverter Start Button”
    The Inverter Assumes the load, and the UPS is normal operation with the load protected.
     
    Caution: Never remove any covers or panels.  There are no user serviceable parts inside.
     