    What would cause the ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot?

    Issue:
    What would cause the ATV630 Ethernet IP option card VW3A3720 to not show up in somove under the Fieldbus A slot?

    Product Line:
    ATV630 with 

    Environment:
    All 

    Cause:
    ATV630 drives firmware is not at 1.5 or greater or you may need to build a project offline and then import the program into Somove. 

    Resolution:

    Checked option 1 and it shows Ethernet IP card.  option 2 is no
    Drive firmware is Version 1.5IEXX  or greater  which is good for the Ethernet IP option card. 

    Next Open up the Somove software:

    Checked and we created a project offline adding the Ethernet IP card for option A

    Now we copied the program from the drive and now it shows up as Ethernet IP under slot A in the Field bus section under Parameter list.