    Ethernet connected Onicon meter is not communicating in Power Monitoring Expert

    Issue
    A translator file is created for Onicon flow meter in PME.  An Ethernet device is created in PME with an IP address, however, the device does not communicate.

    Product Line
    Onicon Flow Meter

    Environment
    Modbus Device Importer (MDI)
    Management Console

    Cause
    A Modbus address is associated with the Onicon device.

    Resolution
    Onicon flow meters have a default Modbus address of 17.  This address should be included in 'Unit ID' of the Ethernet device in Management Console.

    1. In Management Console, open the property of the Ethernet device
    2. Right click and select 'Advanced Properties'
    3. Set the address in 'Unit ID' field

    NOTE: If the Modbus address is not set, it reverts to default of 255.

    Onicon Modbus manual (D-100 Modbus) can be downloaded from Onicon website.