    Video: Sites/Devices cannot be connected in Power Monitoring Expert

    Issue
    Some sites and or devices cannot connect in PME.  The IP addresses are unable to be pinged as well, but Modbus Tester or ION Setup can communicate successfully.

    Product Line
    ION Enterprise 6.0
    SPM7
    PME7.x
    PME8.x

    Environment
    Device / site communications

    Cause
    Customers may block the Ping command through the network for security reasons.  If Ping is blocked, and 'ICMP Timeout' is configured (in Advanced Properties of Site or Device configuration), this will cause them to not connect.

    Resolution
    Open the Advanced Properties section of the site or device by right clicking in the white space and change the 'ICMP Timeout' setting to 0, which is also the default value.