    Why won't the ATV320 drive output full voltage at 60hz?

    Issue:
    Why won't the ATV320 drive output full voltage at 60hz? 

    Product Line:
    ATV320

    Environment:
    All serial numbers

    Cause: 
    Drive ramps to speed (60z) . The max drive output voltage is only 10 volts with "no" drive fault. 

    Resolution:  
    Set  MPC  to COS 
    DRI- > CONF > FULL > DRC- > ASY   
    MPC   [Motor param choice] >  [Mot Power]  = (nPr) , change to COS   [Mot Cos] (COS)