    Power Monitoring Expert 8.2 - why are some device types missing from the DeviceType table in ION_Network, such as Micrologic, Sepam, Compact NSX?

    Issue
    Device types missing from the DeviceType table in ION_Network.

    Product Line
    Power Monitoring Expert (PME) 8.2
    CM2000, CompactNSX A/E, DM6200, DM6300, EM5600, Micrologic A/E/H/P, Momentum PLC A8 WAGES/D10 WAGES
    PM600, SEPAM 10/20/40/48/60/80, VIGILOHM, TWIDO_MOD_PLC_WAGES_D12_D28_D44, PM9C, PM1200

    Environment
    Power Monitoring Expert (PME) 8.2

    Cause
    The ION_Network database has been deleted and has been recreated using the PME Installer in Reconfigure mode.
    If this has been done, the following device types will not get added to the system:

    CM2000
    CompactNSX A/E
    DM6200
    DM6300
    EM5600
    Micrologic A/E/H/P
    Momentum PLC A8 WAGES/D10 WAGES
    PM600
    SEPAM 10/20/40/48/60/80
    VIGILOHM
    TWIDO_MOD_PLC_WAGES_D12_D28_D44
    PM9C
    PM1200

    Resolution
    *Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio.
    Databases should be backed up prior to performing any procedure.*


    To add these device types into the system, open SQL Server Management Studio and execute the SQL script file named 'PME-DeviceDrivers.sql' within a SQL Query window.
    This file is found in the \system\etc\Database\network directory. Running this script will add the missing device types.