    How to program an ATV630 to follow AI3 analog input for mA or DC signal?

    Issue:
    How to program an ATV630 to follow AI3 analog input for mA or DC signal?

    Product Line:
    Altivar 630, process

    Environment:
    All

    Cause:
    Programming, installation

    Resolution:
    AI3 can be configured for both DC scale or mA.
    To perform this go into Complete Settings, Inputs/outputs, and AI/AQ tab, AI3 configuration.
    Set AI3 type according (DC, mA, PTC man, Kty, Pt1000, etc.)
    Set AI3 min type as 4 mA if needed.
    Set AI3 max value as needed.

    To allow the drive to look at AI3 as a speed refererence:

    Go into Complete settings, Command and Reference, assign Reg Freq 1 Config AI3.

     