    How to program an ATV630 to follow AI3 analog input for mA or DC signal?

    Issue:
    How to program an ATV630 to follow AI3 analog input for mA or DC signal?

    Product Line:
    Altivar 630, Altivar Process ATV630

    Environment:
    All

    Cause:
    Programming, installation

    Resolution:
    AI3 can be configured for both DC voltage scale or current in mA.

    To program - from the Main Menu (hit the Home button to go back to the Main Menu), go into Complete Settings, then Input/Output menu.  At the bottom of the screen, select the AI/AQ tab.  Then select AI3 configuration.

    Set AI3 type accordingly (DC, mA, PTC man, Kty, Pt1000, etc.)
    Set AI3 min type as needed.
    Set AI3 max value as needed.

    To tell the drive to follow the AI3 signal as a speed reference - go into Complete Settings, Command and Reference, Ref Freq 1 Config and select AI3.

     