    On ATV320 drive, what would cause register 5202 reading logic input status LI6 not to turn on?

    Issue:
    On ATV320 drive, what would cause register 5202 reading logic input status LI6 not to turn on?

    Product Line:
    ATV320 drive

    Environment:
    All 

    Cause:
    LI6 status is not showing up on register 5202 logic input status. 

    Resolution:
    Reading address 5202 over Canopen or modbus and bit 5 for LI6 is not turning on. 

    Checked PTC assignment and its NO

    Checked with a meter and com to LI6= 24vdc  

    Check the status of Sw1 make sure its source.  

    Check the status of Sw2 make sure its Logic input not PTC.