    Accusine PCS+ Dual operation mode

    Issue
    The Accusine+ can be used as a harmonic filter and power factor correction/Load balancing simultaneously. The total output current will be limited by harmonic current and the reactivar current. 

    product Line
    Accusine PCS+

    Resolution 

    The total output of the harmonic filter in dual mode is governed by the following formula:


    When the total current output of the active filter required exceeds the unit rating, the Accusine PCS+ has a harmonic priority setting to determine which mode has priority.

    Use percentage of harmonic priority to set output current split
    • 100% means output capacity utilized for harmonic correction, then left over can be used for Power factor correction.
    • 0% assigns fundamental (PF correction) current as the primary mode, left over used for harmonic correction.
    The table below describes the relationship between harmonic current the reactive current



     