    After conversion of my SoMachine V3.1 project including an M258 to v4.2, TM5 modules configuration tabs are wrong

    After conversion of a SoMachine V3.1 project including an M258 to SoMachine V4.2, TM5 modules configuration tabs are wrong.
    For example with DI12DE :
    Normally it should be like this :



    But this is what conversion gives:

    Wrong "Outputs" folder is there.

    Furthermore integrated TM5 modules data is not exchanged when converted project is downloaded to a controller.

    It happens when conversion from V3.1 to V4.2 is not executed “directly” :
    When V3.1 project is opened in SoMachine v4.2, a pop-up asks for project conversion. “Yes” should be answered right now.
     
    If conversion is done later using “right click -> update device” then trouble with TM5 modules happen.
     
    This will be corrected in SoMachine V5.