    How to correct error 22321 Liquid:Calculation of Density at base conditions unsuccessful in Realflo?

    Scenario:
    • The scadapack is polling values from the Coriolis Meter.
    • When the Coriolis Meter losses connections or it stop communicating, The Realflo Run liquid will use the default setting parameters.
    • Make sure that correct parameters are entered on the Default value.
    For example: If the default value for the Density was set to 1 when measuring Liquid and the Coriolis meter losses communications then
    the flow computer will used the default value 1 to calculate the flow and will give an error result of 22321 "Liquid:Calculation of Density at base conditions unsuccessful"

    Use the table below for Density default value: