    Video: PME 8.x EWS - Service not enable on the server

    Issue
    In PME 8.x, when attempting to navigate to the EWS endpoint, the page returns an error stating "Service not enable on the server".



    Product Line
    Power Monitoring Expert 8.x
    EcoStruxure™ Web Services

    Environment
    Power Monitoring Expert

    Cause
    EWS, EcoStruxure™ Web Services, is not enabled by default in a PME system.

    Resolution
    *Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

    1. Navigate to the following default directory on the PME server: C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\applications\EWS
    2. Open the 'Web.config' file in Notepad.
    3. Find "0" /> within the 'appSettings' section of the file.
    4. Change the entry to />.



    5. Save the notepad file.