    After modifying a PowerSCADA Expert project, which steps must a user perform to make them active in Runtime.

    Issue
    After modifying a PowerSCADA Expert project, the user would like to know which steps must be taken to make them active in Runtime.

    Product Line
    PowerSCADA Expert 8.2

    Environment
    PowerSCADA Expert Runtime

    Resolution
     
    Changes Being Made Compile Restart
    Client HMI
    Reload
    Alarm Server
    Reload
    Trend Server
    Restart
    I/O Server
    Restart
    Schneider Electric Core Service Host
    Modify existing graphics pages including embedded Cicode Yes No No No No No
    Add completely new graphics page(s) Yes Yes No No No No
    Changes to PowerSCADA users (by using Cicode runtime CreateUser function) No No No No No No
    Changes to Active Directory group membership No No No No No No
    Changes to roles and Windows Active Directory group mapping Yes No No No Yes No
    Changes to users and/or roles (by using the PowerSCADA Studio) Yes No No No Yes No
    Changes to menu properties Yes No No No No No
    Changes to server-side Cicode Yes No No No Yes No
    Add/remove/modify alarm tags Yes No Yes No Yes Yes (if you need to update immediately)
    Add/remove/modify trend tags Yes No No Yes No Yes (if you need to update immediately)
    Add/remove/modify devices and/or variable tags Yes No No Yes No Yes (if you need to update immediately)

    Note: The above table is intended for PowerSCADA Expert 8.2. You may use the table as a reference for previous versions, however there has been no testing to validate these recommendations. 