    PowerChute Network Shutdown fails to Turn UPS off when the Network Management Card AP9617, AP9618, or AP9619 are configured for HTTPS.

    Issue: 
    PowerChute Network Shutdown fails to Turn UPS off when the Network Management Card AP9617, AP9618, or AP9619 are configured for HTTPS.

    Product Line: 
    PowerChute Network Shutdown versions 3.1, 4.X
    with Network Management Cards: AP9617, AP9618, AP9619

    Environment: 
    Supported operating systems for the relevant PowerChute Network Shutdown versions in Product Line above.

    Cause: 
    An SSL handshake error occurs when Java 7 and 8 is installed on the system and PowerChute attempts to communicate with an AP9617, AP9618, AP9619.

    Solution:
    To correct the issue change the communication protocol between the NMC and PowerChute to HTTP. There is no HTTPS solution with PowerChute Network Shutdown versions 3.1 and 4.x
     