    PM8000 displays an incorrect Vln avg value when setting the Volts Mode to Single

    Issue:
    When the PM8000 volts mode is set to Singe, it will display an incorrect value for Vln avg when monitoring a 2 wire single-phase system. 

    Product Line:
    PM8000 series

    Environment:
    Meter's display

    Cause:
    When the device is set to a Volts Mode of Single, Vln avg is the average of Vln a and Vln b. For a 2 wire single-phase system, Vln a is the expected value, and Vln b is equal to 0. Vln avg is then half of the expected value.
    Vln avg = (Vln a + Vln b) / 2 = (Vln a + 0) / 2 = (Vln a) / 2

    Resolution:
    The Vln avg value can be relinked to Vln a using ION Setup. ION Setup can be downloaded here: https://schneider-electric.app.box.com/ionsetuplatest

    Once the device is connected in ION Setup, perform the following:
    1. Enter into Advanced Setup
      1. Right-click on the meter and select Properties...
      2. Navigate to the Tools tab
      3. Select Show Advanced ION Setup
      4. Press OK
    2. Double-click Data Mapping Meas Modules
    3. Double-click Data Mapping Meas 1
    4. Relink the Vln avg input to \Power Meter Modules\MU Power Meter\MU Vln a
    Note: The Vln avg input cannot be linked to \Power Meter Modules\Power Meter\Vln a as multiple inputs cannot be linked to the same value, and Vln a is already linked to the input Vln a in the Data Mapping Meas Module. Therefore, the MU Power Meter module must be used. If you are using PTs and require the MU Vln a be scaled, then the appropriate scaling would need to implemented using an Arithmetic Module.
    1. Click on Send to save the change