    ScadaAddress Not Found error

    Issue
    The following error pops up when Runtime is started:

              
              Warning: No Citect.ini [DNPR]ScadaAddress=x entry found

    Product Line
    PowerSCADA 8.1, 8.2 (applies to any version that supports DNP protocol)

    Environment
    Citect Runtime

    Cause
    A device with DNP protocol is added to the system, however, proper parameters are not configured in Citect.ini file.
     
    Resolution
    Add the following section/parameter to Citect.ini file and restart the Runtime:

    [DNPR]ScadaAddress=3

    Where ScadaAddress defines the DNP address for CitectSCADA with a default value of 3.  The value could be between 0 - 65534.

    NOTE: The value must (may) also be defined in the DNP slave device as the 'Master DNP Address' (only if the slave requires to know the DNP Master address).
     