    Is it possible to disable phase loss detection function in ATS48?

    Disabling the phase loss detection function in ATS48 is only possible only through Somove. The parameter cannot be disabled through graphic terminal. However it is not recommended to disable this function especially in following circumstances:

    - When using ATS48 for its typical applications
    - When using a bypass contactor unless exterior detection methods exist

    For disabling phase loss detection, go to ATS48 parameters in Somove, go to Advanced protections, search for parameter PHP, click on the current value and a warning will appear, press Ok and change the current value to Off. 
      