    What causes LFF3 code on the ATV320 drive?

    Issue:
    What causes LFF3 code on the ATV320 drive?

    Product Line:
    Altivar 320, ATV320

    Environment:
    All

    Cause:
    N/A

    Resolution:
    This is a AI3 4-20 mA loss.  This indicates that the 4-20mA reference on Ai3 and COM is not seen as expected.
    If this function is programmed in error you can disable it by going under CONF, FULL, and I/O.
    Here you will have menus A1C-, A2C-, and A3C-.  These are alarm group 1 - 3 definition parameters.
    One of them must be programmed as AP3 as AP3 is an alarm indicating the absence of 4-20mA signal on input AI3.
    These can always be unassigned to disable this function if not needed.