    Why am I having issues connecting SoMove to an Altivar Drive or Altistart Soft Starter?

    Issue:
    SoMove Troubleshooting:Cannot Connect to SoMove using an Altivar Drive 

    Product Line:
    Altivar Drive (ATV61, ATV71)
    Altivar Machine Drive (ATV12, ATV31, ATV312, ATV32, ATV320, ATV340)
    Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
    Altivar Building Drive (ATV212)
    Altistart Soft-Starters (ATS01, ATS22, ATS48)

    Environment:
    All serial numbers for AC Drive or Softstarter

    Cause:
    Trying to connect to SoMove but cannot

    Resolution:

    Basic Checks
    • Check SoMove Version and DTMs
    • Check to make sure the Drive or Soft-Starter is compatible
      • List of compatible
        • Altivar Drive (ATV61, ATV71)
          Altivar Machine Drive (ATV12, ATV31, ATV312, ATV32, ATV320, ATV340)
          Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)
          Altivar Building Drive (ATV212)
          Altistart Soft-Starters (ATS22, ATS48)
      • Check firmware compatibility

    Using Modbus Serial Cable (TCSMCNAM3M002P) to connect to SoMove:
    • On your Drive:
      • Check wiring
        • Use Schneider Electric cable only (TCSMCNAM3M002P)
        • Check to make sure you are connected to the correct ports. Ports to use are
          • Modbus HMI
          • Modbus/CanOpen
          • Do not use Ethernet or any other ports
      • Check Modbus Network Settings, check the following:
        • Modbus Baud Rate - 19.2 kbps
        • Modbus Format - 8E1 (8N1 for ATS48)
        • Modbus Time Out - 10.0s
    • On your PC:
      • Check Modbus Serial Settings in SoMove
        • Go to Edit Connection/Scan and click on Modbus Serial
        • Go to Advanced Settings (gear picture on right side) and check the following under Configuration tab
          • Connection Type - Serial Line
          • COM Port: COM???
            • Check Device Manager on PC to make sure correct COM Port is configured for the TSX C USB 485 driver
          • Baudrate - 19200kbps
          • Parity - Even
          • Stop Bits - 1 Bit
          • Mode - RTU (8 Bits)
          • Baudrate,parity, and stop bits may need to be modified in SoMove to match settings in drive.
      • Check Modbus Drivers are installed
        • On PC go to your Start then go to All Programs and then Schneider Electric folder
        • Click on Communication Drivers and then Driver Manager
        • Under SCHNEIDER Drivers Management Properties - Drivers Manager tab
          • Check and make sure MODBUS driver is installed
          • If no drivers are found then reinstall SoMove or download
      • Check Modbus Serial settings on PC
        • On task bar right click on Schneider Modbus Serial Driver then go to Configure
        • Under Configuration tab check the following:
          • COM Port: COM???
          • Baud Rate - 19200
          • Stop Bits - 1 Bit
          • Parity - Even
          • Mode (Data Bits) - 8 Bits
    Using Ethernet to connect to SoMove:
    • On Drive
      • Check wiring
        • Use regular Ethernet cable not Modbus
        • Make sure plugged into correct Ethernet port
          • If using Modbus TCP, Ethernet IP or Profinet use dedicated Ethernet port if possible
      • Check Ethernet setting on Drive
        • IP Address
        • Subnet Mask
        • Gateway
        • ModBus network address (if using EthIP or Profinet)
      • Powercycle drive when any Ethernet changes are made
    • On PC
      • Check Ethernet Settings in SoMove
        • Go to Edit Connection/Scan and click on Remote Gateway (for Ethernet IP/Profinet)
        • Go to Advanced Settings (gear picture on right side) and check the following under Configuration tab
          • Connection Type - Remote Gateway (for connecting sing Ethernet IP, Modbus TCP, Profinet...)
          • Remote Gateway - Put in complete IP address when doing Modbus TCP (Modbus over Ethernet) then click Apply and OK then Scan Network and drive should come up.
            • For scenario when doing Ethernet IP or most other protocol is a little different.
            • Put in IP address and leave the last octet as a 0.
            • For instance, IP address for drive is 192.168.10.1 then you will put in 192.168.10.0 for Remote Gateway
              • Next, under Scan tab
                • Scan Mode - Multipoint
                • Connection Type - Single - Set to last octet in IP address
              • For instance, IP address for drive is 192.168.10.1, then Single to 1