    Why can one not see a duration time for a sag event?

    Issue:
    A sag event has occurred on an ION or PowerLogic meter, but the duration does not display through a data log viewer.

    Product Line:
    ION Enterprise 6.0 SP1 / SPM 7.0.1 / PME 7.x / PME 8.x

    Environment:
    Vista

    Cause:
    All meter power quality events (sag, swells, transients) have two separate 'Disturbance Start' and 'Disturbance End' timestamps.  PME uses the difference between these two to calculate the duration.  During a sag event if a meter's control power is wired in parallel to the voltage inputs this can cause the meter to only register the 'Disturbance Start' event.  

    Resolution:
    If a duration time stamp is needed the meter should be wired with separate control power from the voltage inputs such as a battery back up.  This will ensure that if the voltage inputs should go to zero the meter will still remain powered to capture both the start and end events.