    Video: How to generate and configure a PUE (Power Usage Effectiveness) report in Power Monitoring Expert

    Issue
    How to generate and configure a PUE (Power Usage Effectiveness) report?

    Product Line
    Power Monitoring Expert 7.2.x
    Power Monitoring Expert 8.x 

    Cause
    User would like to know how to generate PUE report and learn how the report calculates PUE. 

    Environment
    Generating PUE report from web application. 

    Resolution 
    A video is attached which describes a step-by-step procedure on how to generate and configure PUE reports. 

    PUE calculation: 
    PUE (Power Usage Effectiveness): The ratio between the data center and IT equipment energy measurement values. 
    This value is calculated for each of the required time periods by the following formula:

    PUE = Sum of DataCenter Energy / Sum of IT Equipment Energy

    IT Equipment – The average of the IT equipment power measurement values for each of the
    time periods.

    Data Center - The average of the data center power measurement values for each of the time
    periods.