    What would cause a 4-20mA Loss Warning on an Altivar Process Drive?

    Issue:
    What would cause a 4-20mA Loss Warning on an Altivar Process Drive?
    How to get rid of Red Flashing Warning Light?

    Product Line:
    Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

    Environment:
    All serial numbers for Altivar Process Drive

    Cause:
    Drive is displaying Warning or Error Codes:
    AP1 - AI1 4-20 Loss Warning
    AP2 - AI2 4-20 Loss Warning
    AP3 - AI3 4-20 Loss Warning
    AP4 - AI4 4-20 Loss Warning
    AP5 - AI5 4-20 Loss Warning
    LFF1 - AI1 4-20mA loss
    LFF2 - AI2 4-20mA loss
    LFF3 - AI3 4-20mA loss
    LFF4 - AI4 4-20mA loss
    LFF5 - AI5 4-20mA loss


    Resolution:
    The 4-20mA loss operates with 2 hysteresis: one threshold to activate the 4-20mA loss and the other threshold to allow the reset of this 4-20mA.
    - When the AI value goes under 2mA the drive detects the 4-20mA loss.
    - When the AI value goes over 3mA the drive allows the reset of 4-20mA loss
    - When the AI value drops down pretty close to 2mA the drive displays a 4-20mA Loss Warning

    Possible Remedies:
    - Verify the connection on the analog inputs
    - Check mA signal for possible interference
    - This detected error can be cleared with the [Auto Fault Reset] Atr or manually with the [Fault Reset Assign] rSF parameter after the cause has disappeared

    To Clear 4-20mA Loss if getting Warning Light
    If getting a red warning light flashing on the keypad normally it is because it detects an AI2 or AI3 4-20mA Loss Warning. To clear the warning light try the following:
    • First, disable the 4-20mA warning
      • [Complete settings] [Error/Warning handling] [4-20mA loss]
    • Second, change from 4-20mA to Voltage
      • [Complete settings] [Input/Output] [AI/AQ] [AI2 configuration]
      • [Complete settings] [Input/Output] [AI/AQ] [AI3 configuration]

    Didn’t find what you were looking for?

    Try Searching Again View Our Categories

    Need further assistance?

    Our Customer Care department provides total customer service solutions for our residential, industrial and commercial applications.

    Get Assistance