    Video: How to program an ATV320 for 2 wire control?

    Issue:
    Programming an Altivar ATV320 for 2 wire control?

    Product Line:
    Altivar 320, ATV320

    Environment:
    All

    Cause:
    Setup, programming.

    Resolution:



    From main menu,
    Enter on dial to go to CONF and enter.
    Go down to FULL and enter.
    Go down to I_0- and enter.
    Set TCC for 2C for 2 wire control.
    Set TCT to LEL instead of TRN for level control.
    In transition mode, the drive will need to be powered up before a run command is given.
    In level mode (LEL), the drive logic DI1 has a state of 0 or 1.  If the run command is given it will run upon power up.
    If the run command is not there the drive will wait for one in RDY status.