    Does the HMISCU6B5/8B5 has open wire detection for the temperature input?

    Issue:
    Does the HMISCU6B5/8B5 has open wire detection for the temperature input?

    Product Line:
    HMISCU6B5, HMISCU8B5, thermocouple, PT100, value not going to 0

    Environment:


    Cause:


    Resolution:
    The HMISCU does not offer Thermocouple Broken wire detection.

     When the T/C is broken the temperature reading stays the same.  Therefore if the process where the temperature is changing at least 0.1F every so often logic could be written to detect a broken wire detection.

    Attached an sample Function Block that could imported in the SoMachine project.  It is monitoring the temperation every 10 seconds and if doesn't see a change a broken Thermocouple bit gets set. If 10 seconds is too sensitive then change it to a longer period of time.