    How can I read %I/Q or %M on my M221 M241 M251 M258 LMC058 using Modbus ?

    2 cases have to be considered: M221 or (M241 M251 M258 LMC058).

    M221 :

    %M (internal bits) can be accessed using function codes from the table below (extracted from SoMachine Basic online help).
    Note that %I (physical inputs) and %Q (physical outputs) can not be accessed directly by Modbus.



    M241 M251 M258 LMC058:

    %M (internal bits) cannot be accessed by Modbus.
    But %I (physical inputs) and %Q (physical outputs) can be accessed using function codes from the table below (extracted from SoMachine online help).