    Explanation of error E7875 on LXM32 drive with eSM module

    Issue:
    What is error E7875 on the LXM32 drive with the eSM safety module?

    Product Line:
    LXM32

    Resolution:
    Error E7875 is generated when error E7804 have been triggered 5 times. 
    E7875 is a class 4 error and it requires a power cycle to clear it. 
    E7804 means a deceleration of type QuickStop did not respect the ramp monitored by eSM_dec_Qstop. E7804 is a class 3 error and can be easily reset. 

    In case a safety barrier has been crossed, and was linked to inputs ESTOP_A/B, the system immediately signals an eStop error E780A and generates a QuickStop. 
    The drive decelerates following the ramp configured in RAMPquickstop and simultaneously, the eSM module monitors if the deceleration is at least as fast as the value of parameter eSM_dec_Qstop
    If this is not the case, the eSM module generates the 1st error E7804. After 5 E7804, the eSM module generates error E7875.

    Solution:
    --> Increase the deceleration ramp during eStops.
    --> Add a braking resistor if necessary.
    --> Reduce the load or the load inertia if possible.