    How to program the ATV31/ATV312 drive so that an output status is received when it is running?

    Issue:
     How to program the ATV31/ATV312 drive so that an output status is received when it is running?

    Product Line:
    Altivar 31, Altivar 312

    Environment:
    All

    Cause:
    Run status

    Resolution:
    R1 or R2 relays on the drive can both be used depending on preference.
    R1A and R1C or R2A and R2C.
    Enter on dial (ATV312) or enter on drive (ATV31).
    Scroll down to I-0- menu.
    Find R1 or R2 depending on which one is used.
    Program relay for run.