    What would cause Altivar 61 and Altivar 71 drive to not start with the terminal inputs on +24 and LI1?

    Issue:
    What would cause Altivar 61 and Altivar 71 drive to not start with the terminal inputs on +24 and LI1?

    Product Line:
    Altivar 61/71

    Environment:
    All

    Cause:
    Drive was in HMI mode with the F4 function key set to T/K. 

    Resolution:
    - Check to see if the Functions keys are assigned to T/K  if so push that Function key to put the drive back in Remote mode. 
    - If its already in terminal mode check the supply voltage on LI1 
    - Check Programming in menu 1.6 the command menu to see if the drive is set for terminal control mode. 