    Address Format for a BACnet Device in Scada

    Issue
    In I/O Devices form, what should the 'Address' field be set to?

    Product Line
    PowerScada Expert 8.1

    Environment
    I/O Devices form in the project.

    Cause
    A device communicating with BACnet protocol is being added to Scada.

    Resolution
    NOTES:
    - The default UDP port is 47808.
    - The 'device ID' uniquely identifies each BACnet device and can be in the range of 0 to 4194302.  In the examples below, it is assumed the device ID is 12262.

    The address format for the configuration takes one of the following two structures:

    1. If the default UDP port is used:
         -I
        12262 -I 10.167.167.25

    2. If non-standard UDP port is configured in the device (assume UDP port of 48000):
        -I -U < device UDP port number>
        12262 -I 10.167.167.25 -U 48000



     