    Video: How to install shunt trip or under voltage trip on a PowerPact B-frame breaker

    Issue:
    How to install shunt trip or under voltage trip on a PowerPact B-frame breaker
     
    Product Line:
    PowerPact Molded Case Circuit Breakers
     
    Environment:
    B-frame Circuit Breakers
     
    Cause:
    How to install shunt trip or under voltage trip on a PowerPact B-frame breaker
     
    Resolution:
     
    First, the breaker must be in the tripped position. Once in the tripped position, open the accessory cover, and install the shunt or under voltage in the left slot in the breaker. Push down until it clicks into place. When the cover is closed, the MN (under voltage) or MX (shunt) green tab will be visible through the window. To remove the shunt or under voltage, take a thin object like a screwdriver, slide into the slot in the device, and push it up until it clicks out of place. For further instruction, see video below: