    How can one configure the ATV312 to run upon power up and ramp up to full speed (60 hz)?

    Issue:
    How can one configure the ATV312 to run upon power up and ramp up to full speed (60 hz)?

    Product Line:
    Altivar 312, ATV312

    Environment:
    N/A

    Cause:
    N/A

    Resolution:
    Go into I-0- menu.
    Set TCC to 2C.
    Set TCT to LEL.

    Go into SET- menu.
    Set LSP to value desired in hz.  For example, 60 hz is full speed.

    Once programming is complete and drive powered down apply jumper to LI1 and +24V for run command.
    Note: Drive will run motor as soon as power is applied to the drive with this configuration.