    Digital Output Tags have Bad Quality in Scada when Using ION Protocol

    Issue
    A device profile is created using Profile Editor based on ION protocol, and then exported to a project in PSE.  A device is added to the project based on this profile.  The quality for all digital output tags are 'Bad'.

              

    Product Line
    PowerScada Expert 8.1 (PSE 8.1)

    Environment
    Profile Editor
    Citect Project Editor > Variable Tags

    Cause
    The tag addresses in PSE don't match the digital output labels in the ION device.

    Resolution
    Find out what the output labels are for the digital output modules and modify the tag addresses accordingly.  Here is an example of where to find the label for one of the digital outputs:

              


    Once all tag addresses are modified, PSE is able to find the digital outputs:

              

    Note that the tag addresses can either be modified in Profile Editor or using Variable Tags in Citect Project Editor.
     